| Output Voltage |
Zero to rated voltage
continuously variable with front panel voltage knob |
| Output Current |
Zero to rated current
continuously variable with front panel current knob |
| Line Regulation |
CV±0.01%+2mV; CC±0.01%+2mA |
| Load Regulation |
CV±0.01%+2mV; CC<10mA @
100W;<15mA @ above 100W |
| Ripple & Noise |
CV<0.5mVrms @ 100W;
<1mVrms @ above 100W
CC<1mArms @ 100W; <3mArms @ above 100W |
| Transient Response |
<100µS to within 0.1% of
set voltage (50% to 100% load change) |
| Output Impedance |
<2mW +2mH |
| Operating Range |
0 to 40° C ambient
temperature |
| Display Accuracy |
£0.1%+2 digits |
| Overload Protection |
Automatic crossover from CV to
CC mode |
| Series Connection |
Different models can be
chained to increase output up to 240 Vdc |
| Parallel Connection |
Another same model can be
paralleled to increase output to 24 Amps |
| 5V/5A Fixed Supply |
Regulation£ 10mV;
Ripple & Noise£ 2mVrms; Output: 5V± 0.25 V |
| Tracking Accuracy |
± 0.2%+10mV |
| Operation Mode Switch |
|
Independent:
Series:
Parallel: |
Two fully independent variable
supplies at rated voltage and current and a fixed 5V/5A supply
One variable supply with 2X rated voltage output at rated current. Or, One dual
polarity tracking supply with rated output and current. Plus A 5V/5A supply
One variable supply with rated voltage at 2X rated current and a fixed 5V/5A supply |
| Power Requirement |
100/120/220/240±10% Vac;
50/60Hz single phase |
| Accessories Supplied |
Power cord; hook-up leads;
instruction manual |